ARC1 Series Miniature Circuit Breaker ARC1-63-2P-6ka
Rated Current : 6A、10A、16A、20A、25A、32A、40A、50A、63A
Number Of Poles : 2P
Rated Working Voltage : 230/400
Share:
  • Product Overview
  • Environment of use
  • Technical specifications
  • Size structure
  • Download information

Scope of application

ARC1-63 series high breaking small circuit breaker has advanced structure, reliable performance, high breaking capacity, beautiful and compact appearance, etc. The shell and three parts are made of impact resistant and high flame retardant materials. Suitable for AC 50Hz or 60Hz, rated working voltage below 400V, rated current below 63A. It is mainly used for overload and short-circuit protection of lighting, distribution lines and equipment in office buildings, residences and similar buildings, and also for infrequent line conversion under normal conditions.


  • Comply with the standard: IEC60898, GB10963.1

  • Operating temperature:-35C~+70C, the average temperature within 24h does not exceed +35*C

  • Altitude:S2000m

  • Atmospheric conditions:The relative humidity of the air at the installation site is ≤50% at +40C, 90% at maximum

0.jpg

Outer packaging information (dimensions Weight)

Model number

Minimum

order

quantity

Product size mm

(L*W*H)

Weight

Packing metho

(wooden box/carton)

Number of boxes

Inner box size cm

(L*W*H)

Outer box size cm

(L*W*H)

Box weight

(g)

ARC1-63-2P12


1222.4cm*9cm*8cm

0.jpg



Accessories and Accessories

0.jpg

1-英文.jpg

Main specifications and parameters

Rated operating voltage (V)

Rated current (A)

Polar Number

Rated short-circuit breaking capacity

Note

Expected current of test line (A)

Power Factor

230/400

6、10、16、20、25、32、40

1P,2P,3P,4P

4500

0.65~0.70


400

4500

0.65~0.70


230/400

50、63

1P,2P,3P,4P

4500

0.75~0.80


400

4500

0.75~0.80



Overcurrent decoupling characteristics

Test current (A)

Rated voltage (V)

Specified time

Expected results

Start State

Note

1.13In

All values

t≥1h

No unbuttoning

cold state

The current rises steadily to the specified value within 5s

1.45In

All values

t<1h

Disconnect

Thermal

The current rises steadily to the specified value within 5s

2.55In

In≤32A

1<t<60s

Disconnect

cold state

Close the auxiliary switch to turn on the current

2.55In

In>32A

1<t<120s

Disconnect

cold state

Close the auxiliary switch to turn on the current

5In(Type C)

All values

t≥0.1s

No unbuttoning

cold state

Close the auxiliary switch to turn on the current

10In(Type C)

All values

t<0.1s

Disconnect

cold state

Close the auxiliary switch to turn on the current

10In(Type D)

All values

t≥0.1s

No unbuttoning

cold state

Close the auxiliary switch to turn on the current

14In(Type D

All values

t<0.1s

Disconnect

cold state

Close the auxiliary switch to turn on the current


Shape and size

image.png

Scan QR Code and Follow with WeChat Accounts to get all sample books